Characteristics
Parameters of input and output signals of local SHC
Redundant LSHC
Signal type |
Parameters |
Quanity |
Unified analog signals (AS) |
(-5 +5, -10 +10) V (0 - 5, 0 - 10) V (0-5, 0-20, 4-20) mA |
|
Signals from temperature sensors of any standard calibrations, including: |
GOST 6651 GOST RU 8.585 |
- 96 redundant inputs, expandable |
From the speed sensors From the frequency and unit-counting sensors
|
(0,1 - 15,0) V (0-10) kHz |
- 3 triple frequency inputs - 6 single counters |
Two-positional signals |
"Dry" contacts and/or potential signals (24 … 220) V |
- 6 groups triple signals (each group contains 32 voltage signals, or 64 "dry" contacts), expandable |
Control commands as relay contacts |
~220 V <1,0 A; =220 V <0,4 A; =24 V <4 A |
– 96 redudant (triple) outputs |
Regulation signals for the positioners (DAC) and actuators the fixed speed (PWM) |
4-20 mA 24 V, < 0,1 A |
- 4 doubled outputs (DAC) - 6 doubled outputs (PWM), expandable |
Not redundant LSHC
Signal type |
Parameters |
Quanity |
Unified analog signals (AS) |
(-5 +5, -10 +10) V (0 - 5, 0 - 10) V (0-5, 0-20, 4-20) mA |
- 128 ADC inputs, expandable |
Signals from temperature sensors of any standard calibrations, including: resistance thermal converters Cu, Pt |
GOST 6651 GOST RU 8.585 |
- 48 inputs, expandable |
From the speed sensors From the frequency and unit-counting sensors |
(0,1 - 15,0)V (0-10) kHz |
- 3 frequency inputs - 2 single counters |
Two-positional signals |
"Dry" contacts and/or potential signals (24 … 220) V |
-160, expandable |
Control commands as relay contacts, commuting electrical circuits |
~220 V <1,0 A =220 V <0,4 A =24 V <4 A |
- 80 outputs, expandable |
Regulation signals for the positioners (DAC) |
4-20 mA |
- 16 outputs (DAC), expandable |
and actuators the fixed speed (PWM) |
24 V, < 0,1 A |
- 12 outputs (PWM), expandable |
The basic error of measurement and alarm
For the unified signals - 0,1 - 0,2 %;
For low level signals - 0,1 - 0,3 %;
For tachometric (number-pulse) signals - 0,05 %;
Dynamic characteristics
LSHC:
Cycle time input from sensors (analog, frequency, digital) and data processing - 0.01 s
Cycle time of the command output logic control - 0.2 s
Cycle time "slow" regulating channels - a multiple of 0.2 s
The cycle time of the "fast" channel protection and control - 0.01 s
Automated workplace (upper level):
Rate of interchanging with LSHC - 10-100 Mbod
Refresh time on the screen - no more than 0.5 s
Ttime delay output signals on the screen - no more than 0.5 s
Time delay the output remote command - no more than 0.2 s (through the physical channel - no more than 0.02 s).
Average time to failure
Redundant LSHC:
Type of failure |
Operating time |
Failure of emergency protection |
150000 h |
False activation of the emergency protection, fault control, failure to of regulation |
100000 h |
Failure of monitoring |
80000 h |
Not redundant LSHC:
Type of failure |
Operating time |
Failure of emergency protection |
80000 h |
False activation of the emergency protection, fault control, failure to of regulation |
80000 h |
Failure of monitoring |
60000 h |
Power supplies LSHC:
The basic network (220+22-33) V, (50±1) Hz
Reserve network (220+22-33) V, (50±1) Hz, or (220+22-33) V DC
Bumpless switching with the basic network to reserve network and back is provided by LSHC
Automated workplace power supplies
Network (220+22-33) V, (50±1) Hz;
Source of an uninterrupted food of an automated workplace in a current of 30 minutes
Working conditions LSHC
(minus 25 – plus 60) °С air
Dust, evaporation of oil and water, vibration, shock - typical for rooms of technological units
DC (and AC, 50 Hz) magnetic field of intensity up 100 A/m